LR9F69
Main | |
---|---|
range | TeSys |
product name | TeSys LRF |
device short name | LR9F |
Product or Component Type | Electronic thermal overload relay |
relay application | Motor protection |
Product Compatibility | LC1F115…LC1F185 |
network type | AC |
thermal overload class | Class 10/20 IEC 60947-4 |
thermal protection adjustment range | 90…150 A |
signalling function | Pre-alarm indicator |
Complementary | |
---|---|
Network Frequency | 50/60 Hz |
[Us] rated supply voltage | 24 V DC alarm circuit |
supply voltage limits | 17…32 V alarm circuit) |
mounting support | Direct on contactorPlate |
tripping threshold | 1.05 +/- 0.06 In alarm IEC 60947-4-11.12 +/- 0.06 In tripping IEC 60947-4-1 |
surge withstand | 4 kV IEC 61000-4-5 |
contacts type and composition | 1 NO + 1 NC |
[Ith] conventional free air thermal current | 5 A control circuit |
[Ue] rated operational voltage | 1000 V AC 50/60 Hz power circuit VDE 0110 group C |
[Ui] rated insulation voltage | Power circuit 1000 V AC IEC 60947-4 |
[Uimp] rated impulse withstand voltage | 8 kV IEC 60947-1 |
phase failure sensitivity | Tripping in 4 s +/- 20 % IEC 60947-4-1 |
reset | Manual reset |
control type | Dial White full-load current adjustmentTest button RedPush-button resetPush-button Red stopSelector switch load balancingSelector switch class 10/20 |
local signalling | Trip indicatorAlarm |
temperature compensation | -4…158 °F (-20…70 °C) |
current consumption | <= 5 mA no-load |
switching capacity for alarm | 0…150 mA |
maximum voltage drop | <2.5 V closed state |
connections – terminals | Control circuit screw clamp terminals 1 0.00…0.00 in² (0.75…2.5 mm²) flexible – with cable endControl circuit screw clamp terminals 1 0.00…0.00 in² (0.75…2.5 mm²) solidControl circuit screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²) flexible – without cable endControl circuit screw clamp terminals 2 0.00…0.00 in² (1…1.5 mm²) flexible – with cable endControl circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible – without cable endControl circuit screw clamp terminals 2 0.00 in² (1 mm²) solidPower circuit lugs-ring terminals M8Alarm circuit screw clamp terminals 1 0.00…0.00 in² (0.5…1.5 mm²) flexible – without cable end |
tightening torque | Control circuit 1.2 N.m screw clamp terminalsPower circuit 18 N.m screw clamp terminalsAlarm circuit 0.45 N.m screw clamp terminals |
height | 3.78 in (96 mm) |
Width | 4.53 in (115 mm) |
depth | 4.86 in (123.5 mm) |
Net Weight | 1.95 lb(US) (0.885 kg) |
Environment | |
---|---|
standards | IEC 60255-17VDE 0660EN 60947-4-1IEC 60255-8IEC 60947-4-1 |
Product Certifications | CSAULUKCA |
protective treatment | TH |
IP degree of protection | IP20 conforming to IEC 60529 |
ambient air temperature for operation | -4…131 °F (-20…55 °C) IEC 60255-8 |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
operating altitude | <= 6561.68 ft (2000 m) without derating |
fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
mechanical robustness | Shocks13 Gn for 11 ms IEC 60068-2-7Vibrations 5…300 Hz2 Gn IEC 60068-2-6 |
dielectric strength | 6 kV 50 Hz IEC 255-5 |
electromagnetic compatibility | Resistance to electrostatic discharge 6 kV in indirect mode IEC 61000-4-2Resistance to electrostatic discharge 8 kV in air IEC 61000-4-2Radiated radio-frequency electromagnetic field immunity test 10 V/m IEC 61000-4-3Fast transients immunity test 2 kV IEC 61000-4-4 |
Ordering and shipping details | |
---|---|
Category | 22334 – CONTACTOR,F-LINE,OVERLOADS |
Discount Schedule | I12 |
GTIN | 3389118057548 |
Nbr. of units in pkg. | 1 |
Package weight(Lbs) | 31.89 oz (904 g) |
Returnability | No |
Country of origin | FR |
Packing Units | |
---|---|
Unit Type of Package 1 | PCE |
Package 1 Height | 5.91 in (15 cm) |
Package 1 width | 6.30 in (16 cm) |
Package 1 Length | 5.12 in (13 cm) |
Contractual warranty | |
---|---|
Warranty | 18 months |
Peso | 0.904 kg |
---|---|
Dimensiones | 13 × 16 × 15 cm |
Capacidad | |
Marca | |
Modelo | |
Sistema | 3 Polos |
There are no reviews yet.