GB2CD20

Main
rangeTeSys
product nameTeSys GB2
device short nameGB2
Product or Component TypeCircuit breaker
Device ApplicationControl
poles description1P + N
network typeAC/DC
utilisation categoryCategory A IEC 60947-2DC-12 IEC 60947-5-1DC-13 IEC 60947-5-1
network frequency50/60 Hz IEC 60947-2
breaking capacity2 kA Icu 110 V AC 50/60 Hz IEC 60947-21.5 kA Icu 230/240 V AC 50/60 Hz IEC 60947-21.5 kA Icu 24 V DC IEC 60947-2
[Ics] rated service short-circuit breaking capacity75 % 110 V AC 50/60 Hz IEC 60947-275 % 230/240 V AC 50/60 Hz IEC 60947-2
trip unit technologyThermal-magnetic
magnetic tripping current165 A
Complementary
Mounting ModeBy clips
Mounting SupportRailPlate
mounting positionVerticalHorizontal
Control TypeToggle
Line Rated Current12 A
[Ue] rated operational voltage250 V AC 50/60 Hz IEC 60947-2277 V AC 60 Hz CSA C22.2 No 235277 V AC 60 Hz UL 107748 V DC
[Uimp] rated impulse withstand voltage4 kV IEC 60947-2
power dissipation per pole2 W
mechanical durability8000 cycles
electrical durability8000 cycles
connections – terminalsconnector 1 0.00…0.01 in² (0.75…6 mm²)solid without cable end connector 2 0.00…0.01 in² (0.75…4 mm²)solid without cable end connector 1 0.00…0.01 in² (0.75…4 mm²)flexible with cable end connector 2 0.00…0.00 in² (0.75…2.5 mm²)flexible with cable end
tightening torque10.62 lbf.in (1.2 N.m) connector
mechanical robustnessShocks 22 Gn for 20 ms IEC 60068-2-27Vibrations 5 Gn, 5…110 Hz IEC 60068-2-6
Quantity per SetSet of 6
9 mm pitches2
Height2.91 in (74 mm)
Width0.59 in (15 mm)
Depth2.64 in (67 mm)
Net Weight0.15 lb(US) (0.07 kg)
Environment
standardsEN/IEC 60947-1EN/IEC 60947-2CSA C22.2 No 235UL 1077
Product CertificationsULCSA
protective treatmentTC
IP degree of protectionIP20 IEC 60529
ambient air temperature for operation-4…140 °F (-20…60 °C)
Ambient Air Temperature for Storage-40…176 °F (-40…80 °C)
fire resistance1760 °F (960 °C) IEC 60695-2-1
operating altitude9842.52 ft (3000 m)
Ordering and shipping details
Category22631-TELE CIRCUIT BREAKER (GB2)
Discount ScheduleI
GTIN3389110214963
Nbr. of units in pkg.1
Package weight(Lbs)2.12 oz (60.0 g)
ReturnabilityNo
Country of originFR
Packing Units
Unit Type of Package 1PCE
Package 1 Height0.59 in (1.5 cm)
Package 1 width0.59 in (1.5 cm)
Package 1 Length2.76 in (7.0 cm)
Unit Type of Package 2BB1
Number of Units in Package 26
Package 2 Weight13.47 oz (382.0 g)
Package 2 Height3.23 in (8.2 cm)
Package 2 width3.86 in (9.8 cm)
Package 2 Length3.15 in (8.0 cm)
Unit Type of Package 3S02
Number of Units in Package 372
Package 3 Weight10.78 lb(US) (4.888 kg)
Package 3 Height5.91 in (15.0 cm)
Package 3 width11.81 in (30.0 cm)
Package 3 Length15.75 in (40.0 cm)
Contractual warranty
Warranty18 months
SKU: GB2CD20 Categoría: Etiqueta:
Peso0.06 kg
Dimensiones7 × 1.5 × 1.5 cm
Marca

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “TeSys GB2 thermal magnetic circuit breaker, 1 P + N, 12 A, Id = 165 A GB2CD20”

There are no reviews yet.

Aún no has visto ningún producto.

SHOPPING CART

close
× ¿Cómo puedo ayudarte?